ANSUL CLEANGUARD+® Clean Agent Fire Extinguishers

Nationwide shipping available. Stocking and shipping support for facilities, contractors, integrators, and fire‑equipment dealers across the U.S.

Fast Facts

  • Agent: FK‑5‑1‑12 (clean, residue‑free, electrically non‑conductive)
  • Fire Classes: A, B, and C (model‑dependent ratings below)
  • Sizes/Models: CA03VB (3.5 lb), CA07 (7.5 lb), CA13 (13 lb), CA25 (27.75 lb), CA14‑NM (14 lb MR Conditional)
  • Listings & Approvals: UL/ULC (select models also USCG with approved bracket)
  • Warranty: 6‑year limited (from delivery to original end‑user)
  • Operating Temp: –40 °F to 120 °F (–40 °C to 49 °C)
  • Environment: 0 ODP, <1 GWP, ~5‑day atmospheric lifetime (agent)
  • Maintenance: Rechargeable; hydrostatic test every 12 years (per model data sheet)

Why clean agent? No cleanup, no residue, and no conductive risk to energized equipment—ideal for protecting electronics, servers, labs, artifacts, and control rooms where downtime and collateral damage are unacceptable.

What Is FK 5 1 12?

FK‑5‑1‑12 is a next‑generation, clean, non‑conductive suppression agent that discharges as a liquid and instantly flashes to a gas for efficient knock‑down and extended effective range. It’s non‑corrosive, leaves no residue, and has excellent people‑ and asset‑protection characteristics (low toxicity profile; LOAEL 10%). Environmentally, FK‑5‑1‑12 has zero ozone‑depletion potential (ODP) and ultra‑low global‑warming potential (<1 GWP) with an atmospheric lifetime measured in days, not years.

Fast Facts

Tip: Select the model by hazard type, desired UL rating, and required discharge time/effective range. We can help you size and place units for your occupancy and AHJ requirements.

Standard Models (UL/ULC Listed)

ModelAgent (lb)UL/ULC RatingDischarge TimeEffective RangeCharged Wt.H × W × DUSCG Classification*Bracket Part No.
CA03VB3.52‑B:C8.9 s8–10 ft6.08 lb14‑1/4″ × 5‑3/4″ × 3‑3/8″24610
CA077.55‑B:C8.2 s8–10 ft12.12 lb16‑3/4″ × 8‑1/2″ × 4‑7/16″Type B:C Size I(Bracket included)
CA1313.01‑A:10‑B:C10.7 s10–12 ft20.08 lb20‑1/2″ × 8‑1/4″ × 5‑1/4″Type B:C Size I429146
CA2527.752‑A:10‑B:C18 s14–16 ft39.84 lb23‑7/8″ × 9‑3/4″ × 7‑3/8″Type B:C Size I30937

*USCG approvals require the approved bracket and proper marine installation.

MRI‑Room Model (MR Conditional, UL/ULC Listed)

ModelUse CaseAgent (lb)UL/ULC RatingDischarge TimeEffective RangeCharged Wt.H × W × D
CA14‑NMMR Conditional to 7.0 tesla; non‑magnetic stainless shell/valve/hose/nozzle14.01‑A:10‑B:C11.0 s10 ft19.16 lb14‑3/4″ × 9‑1/4″ × 7‑1/8″

Hydrostatic Test Interval: 12 years (all models).
Operating Temperature: –40 °F to 120 °F across the range.

Performance Snapshot (UL Panel Guidance)

  • CA13: Class A 8 ft × 8 ft panel; Class B 10 ft² (novice) / 25 ft² (experienced)
  • CA25: Class A 10 ft × 10 ft panel; Class B 10 ft² (novice) / 25 ft² (experienced)

(UL defines “novice operator” as minimal experience using a portable extinguisher.)

Clean‑Agent Comparison (At‑a‑Glance)

 

Criteria

FK‑5‑1‑12 (CLEANGUARD+)

HALOTRON BrX™

HALOTRON I

Ozone Depletion Potential

0

0.0028

0.014

Global Warming Potential

< 1

0.26

Low

Atmospheric Lifetime

~0.014 yr (~5 days)

~0.013 yr

~1.3 yr

Cardiotoxicity LOAEL (higher = less toxic)

10%

1%

2%

Cardiotoxicity NOAEL

< 10%

0.5%

1%

Minimum Approved Room Volume**

   

2‑B:C: 40.3 ft³

   

5‑B:C: 86.3 ft³

   

1‑A:10‑B:C: 149.6 ft³

   

2‑A:10‑B:C: 319.3 ft³

   

2‑B:C: 427 ft³

   

5‑B:C: 896 ft³

   

1‑A:10‑B:C: 2988 ft³

   

2‑B:C: 350 ft³

   

5‑B:C: 700 ft³

   

1‑A:10‑B:C: 1540 ft³

   

2‑A:10‑B:C: 2170 ft³

   

Notes:
Minimum room volumes shown are per UL 1093/2129 guidance; volumes must be larger for more toxic agents.
Always verify agent and room size suitability for your application and occupancy.

Where CLEANGUARD+ Shines

  • Selection & placement follow NFPA 10 and your Authority Having Jurisdiction (AHJ). Ratings/classes and travel distances depend on hazard type and occupancy.
  • Mounting at accessible heights with approved brackets is required; several models include or specify a factory bracket.
  • Marking & signage: ensure visibility, access, and clear pathways.

We can help match ratings, quantities, and placements to your floor plan and hazard profile, and coordinate with your AHJ.

Placement, Installation & Compliance (Quick Guide)

  • Selection & placement follow NFPA 10 and your Authority Having Jurisdiction (AHJ). Ratings/classes and travel distances depend on hazard type and occupancy.
  • Mounting at accessible heights with approved brackets is required; several models include or specify a factory bracket.
  • Marking & signage: ensure visibility, access, and clear pathways.

We can help match ratings, quantities, and placements to your floor plan and hazard profile, and coordinate with your AHJ.

Inspection, Maintenance & Service

HT (1)
  • Monthly visual inspections ensure each unit is present, accessible, undamaged, and fully charged.
  • Annual maintenance by a licensed technician is recommended/required to verify mechanics, labeling, and readiness.
  • After any discharge – even for a brief test – units must be recharged.
  • Hydrostatic test: every 12 years for CLEANGUARD+ models (label/data sheet governs).
  • Recordkeeping: maintain tags and service records; QR‑coded nameplates simplify documentation.

Need help? We offer recharge, hydrostatic testing, and walk‑in service support at our St. Petersburg facility, plus shipping of recharged units to enterprise sites and dealer branches nationwide.

Accessories & Brackets

  • Wall brackets: Model‑specific (see table above).
  • Vehicle/marine mounting: Use the approved bracket to maintain USCG listing where applicable.
  • Covers & cabinets: Metal, plastic, and recessed cabinets available for architectural integrations.
steptodown.com191601
Fireboy Boat Systems-min

Ordering & Nationwide Shipping

  • Single units, case‑packs, or palletized shipments available.
  • Professional packing helps prevent transit damage; units ship pressurized and leak‑tested.
  • Ground service is typically used for pressurized cylinders; expedited options available where carrier policy allows.
  • Multi‑site rollouts: we can kit, label, and drop‑ship to each location with consolidated invoicing.

Request a quote: include model(s), quantities, ship‑to ZIP, and any bracket/cabinet needs. We’ll confirm lead times and freight.

FAQ’s

Are CLEANGUARD+ extinguishers safe for energized equipment?

Yes. FK‑5‑1‑12 is electrically non‑conductive and leaves no residue, making it ideal for energized circuits, servers, and control panels.

CLEANGUARD+ models are UL/ULC listed and tested to ANSI/UL 2129/711 with model‑specific ratings. Your AHJ/NFPA 10 governs placement and count.

FK‑5‑1‑12 offers 0 ODP, <1 GWP and a very short atmospheric lifetime. It also shows a more favorable cardiotoxicity profile and much smaller minimum room volume requirements for approved use when compared to many halocarbons. See the comparison above.

Yes. CA14‑NM is MR Conditional (tested to 7.0 T) with a stainless, non‑magnetic assembly for mounting inside MRI rooms.

Perform monthly visual inspections; schedule annual maintenance by a licensed technician; plan hydrostatic testing every 12 years (per model data sheet/label); and recharge after any discharge.

Yes—nationwide shipping is available. Most units ship via ground service due to carrier rules for pressurized cylinders. We’ll handle the packaging and logistics.

Yes—surface, semi‑recessed, and recessed cabinets; vehicle and marine brackets; decals and ID signs are available.

Why Order from Serviced Fire Equipment

  • Clean‑agent expertise: We stock, service, and ship modern clean‑agent units every day.
  • Dealer‑friendly: Bulk pricing and pallet programs for integrators and fire‑equipment dealers.
  • Real support: Sizing, placement, and documentation help; quick turns; reliable packing.
  • Walk‑in service: Recharge, hydro, CO₂ fills, and more at our St. Petersburg shop.

Get a Quote / Talk to a Human

Serviced Fire Equipment, Inc.
3200 62nd Ave N, St. Petersburg, FL 33702
Call: (727) 440‑4290 • (727) 743‑0551
Email: Daniel@ServicedFireEquipment.com

Tell us your model(s), quantities, ZIP, and any mounting/cabinet needs. We’ll size the right units, confirm lead time, and ship fast—nationwide.